The SKP50... controls the differential pressure in the gas supply line in function of the differential pressure in the supply air duct.
The air / gas volume ratio thus remains constant regardless of air volume changes.
The SKP50... also provides the functions of a safety shutoff valve to EN 161 when used in connection with Landis & Staefa gas valves type VG...
Control of the air / gas volume ratio on multi-stage or modulating gas burners with a central or decentral air supply.
Major fields of use:
-
In burner plants with integrated heat recovery systems
-
On burners with an adjustable air / gas mixing facility in the burner head
-
In plants where, in the case of load changes, the pressure conditions in the burner and in the combustion chamber do not change in a linear fashion
In plants with negative pressures on the gas or air side
With the SKP50... - in contrast to conventional compound control - air volume variations caused by
-
mains voltage fluctuations
-
dirty fan wheels
-
changes in the combustion chamber pressure
-
associated heat recovery systems
have no impact on the quality of the combustion process.
When using the SKP50..., a separate gas pressure governor is not required. Since the integrated gas pressure controller does not cause any additional pressure losses, a smaller valve size than usual can be chosen on most applications. The usual measures required for ensuring the minimum air volume must also be taken when using the SKP50....
|